I'm about to install my first "Zincalume" metal roof, about 20square, on a section of my house. All the decking/sheathing is installed and covered with ice and water shield. I have the option to add 1x4 spruce sleepers on top of the underlay at a 45 degree angle fastened to the rafters (24" on center) and spaced about 18" apart. If I do so I believe ventilation will be improved and allow me to some day insulate the attic. But I have few concerns about how to best proceed.
1) Are bright common nails ok to fasten the sleepers? how about coated sundeck screws? or must I absolutely use galvanized nails?
2) Given the 3/4" air space above the underlay if I add the sleepers, does condensation (when the dew point and temperature meet, which may be affected by heat from inside the house?) have more or less of a chance of forming under the metal and running down to meet the sleepers and compromising them - given they must be untreated wood to maintain the integrity of the zincalume?
3) Is there a reason why the lapping of the underlay needs to be "at least 6"? Multiple people have told me this, but why? I think even 4" of merged and melted tar substance should be good enough, or?
4) Is it true that underlay breathes through the seams and overlaps? Then wouldn't less overlap make breathing easier?
Thanks for any and all insights into these particulars.
Regards,
Mark
Quality Demonstrated
11/26/2019
Thanks Mark. There is always much that can be discussed regarding situations like these. So, please feel free to call me at 1-800-543-8938 ext 201.
I would suggest galvanized nails for the battens if you go that route. I do not think that the airspace created by battens changes the potential for condensation. Your attic ventilation and also the ice and watershield help reduce the potential for condensation on the back of the metal roofing. So, on the underlayment overlap, you're talking about ice and watershield? It does not breathe at all, and the seams are sealed so they cannot breathe. Always follow manufacturer recommendations as far as overlap size.
Isaiah Industries, Inc.
11/27/2019